How Much Load Can a Raised Floor Take? A Guide to Raised Floor Load Ratings

Raised floor panel load testing rig at the Rhino factory

There is no single answer to how much load a raised floor can take, because it depends on the panel grade, the pedestals, the stringers and the test method. The figures on this page come from the manufacturers' published technical data. Before ordering, the project engineer should check equipment loads against these values.

What each load rating means

RhinoROC® (cement-filled steel panels)

Values from the RhinoROC technical manual, tested on actual understructure with bolted stringers. Panels are 600 × 600 mm, and all grades are interchangeable within the same floor.

ItemROC100ROC200ROC300
Concentrated load3.56 kN (800 lbs)4.45 kN (1,000 lbs)5.56 kN (1,250 lbs)
Approximate equivalent in kilogram-force≈ 363 kgf≈ 454 kgf≈ 567 kgf
Ultimate load (safety factor 3.0)10.68 kN13.34 kN16.68 kN
Uniform load14 kN/m²17 kN/m²19 kN/m²
Rolling load, 10 passes2.67 kN3.56 kN4.45 kN
Rolling load, 10,000 passes1.78 kN2.67 kN3.56 kN
Impact load0.67 kN0.67 kN0.67 kN
System weight (at 150 mm FFH)42 kg/m²45 kg/m²48 kg/m²
Typical useGeneral offices, meeting roomsServer rooms, control rooms, UPS roomsHeavy equipment cabinets or areas with regular trolley traffic

Intertek tested the ROC200 system (ROC200 panels, RSP103 pedestals and RSL600 stringers) to the CISCA Recommended Test Procedures for Access Floors 2007, sections 1 to 8, in 2016. The kilogram-force values in the table are approximate unit conversions (1 kN ≈ 102 kgf), not tested values.

RhinoEU® (calcium sulphate panels)

EU1000 values from Rhino's calcium sulphate panel specification sheet: concentrated load 4.5 kN, uniform load 12 kN/m² and ultimate load 13.5 kN, tested to PSA MOB PF2 PS/SPU. (The specification sheet lists these as 450 kg, 1,227 kg and 1,750 kg; a direct unit conversion gives approximately 459, 1,224 and 1,734 kgf.) Other grades follow the RhinoEU technical data on this website. Deflection at the centre of the panel edge is no more than 2.5 mm, with a safety factor of three times the static load.

ItemEU800EU1000EU1250EU1500
Concentrated load3.00 kN4.50 kN5.56 kN6.67 kN
Uniform load8.00 kN/m²12.00 kN/m²16.00 kN/m²20.00 kN/m²
Ultimate load9.00 kN13.50 kN16.68 kN20.01 kN
System weight (bare panel)56 kg58 kg62 kg68 kg

Lindner NORTEC

Lindner rates its floors to EN 12825, load and deflection classes 1A to 5A, with point loads from 2 kN (4 kN breaking load) to 5 kN (10 kN breaking load). An example from Lindner's technical documentation: a 36.5 mm panel in class 3A has a 4 kN point load and an 8 kN breaking load, with a safety factor of 2. Because these values follow EN 12825, they cannot be compared directly with Rhino's CISCA figures. ANBS can supply data sheets for each grade.

How to choose a grade by load

  1. Find the weight of the heaviest equipment, such as racks, UPS cabinets or control panels, and the number of feet or castors.
  2. Divide the weight by the number of feet and compare the result with the panel's concentrated load.
  3. If trolleys or cabinet moves cross the floor regularly, check the rolling load as well.
  4. For storage or document rooms, check the uniform load per square metre.
  5. Send the equipment list to the RHINO team in Thailand. We will recommend a grade, and different grades can be used in the same room, for example ROC100 in the office area and ROC200 in the server room.

Fire test results

See all standards under standards and testing.

Products

Further reading

Request a raised floor quotation

Contact Somsiri (Ple) of the RHINO team in Thailand. Send us the floor area, room type and equipment list, and we will recommend a grade and send a quotation, or use the quote form. Our office: 111 S.K.V Building, 4th floor, Soi Sansabai, Sukhumvit 36, Klongton, Klongtoey, Bangkok 10110 · Mon–Fri 9 AM–5 PM · (02) 661-2990 · (02) 259-1366 ext. 112.