RhinoROC® cement-filled steel raised floor

RhinoROC is Rhino's main raised floor panel: cold-rolled steel, resistance-welded and filled with cement, on a 64-dome bottom shell with cross-beams and 140 welds. The Rhino team in Thailand (ANBS) supplies and installs three grades: ROC100, ROC200 and ROC300.
Choose the grade by load
3.56 kN concentrated load. For general offices, meeting rooms and open-plan floors.
4.45 kN concentrated load. For server rooms, control rooms and UPS rooms, usually with anti-static HPL.
5.56 kN concentrated load. For heavy equipment cabinets or areas with regular trolley traffic.
Applications
ROC100 with carpet tiles or vinyl laid on top. Power and data run under the floor, so outlets can move when the desk layout changes.
ROC200 or ROC300 with anti-static HPL, plus perforated airflow panels in front of the racks.
Control rooms in factories, power plants and transport systems use ROC200 to carry consoles and control cabinets.
Technical specifications
Bare: powder-coated epoxy finish, for carpet tiles or vinyl laid on site
| Item | ROC100 | ROC200 | ROC300 |
|---|---|---|---|
| Panel size (mm) | 600 x 600 | 600 x 600 | 600 x 600 |
| Panel thickness | 33.50 mm | 33.50 mm | 34.00 mm |
| Panel weight | 13.00 kg | 14.00 kg | 15.00 kg |
| System weight | 42.00 kg | 45.00 kg | 48.00 kg |
| Concentrated load | 3.56 kN | 4.45 kN | 5.56 kN |
| Uniform load | 14.00 kN | 17.00 kN | 19.00 kN |
| Ultimate load | 10.68 kN | 13.34 kN | 16.68 kN |
Covered: factory HPL or vinyl finish with trim edge
| Item | ROC100 | ROC200 | ROC300 |
|---|---|---|---|
| Panel size (mm) | 600 x 600 | 600 x 600 | 600 x 600 |
| Panel thickness | 35.00 mm | 35.00 mm | 36.00 mm |
| Panel weight | 14.00 kg | 15.00 kg | 16.00 kg |
| System weight | 45.00 kg | 48.00 kg | 51.00 kg |
| Concentrated load | 3.56 kN | 4.45 kN | 5.56 kN |
| Uniform load | 14.00 kN | 17.00 kN | 19.00 kN |
| Ultimate load | 10.68 kN | 13.34 kN | 16.68 kN |
The system sits on RSP101 / RSP201 pedestals with RSL600 rectangular tube stringers. Every grade is 600 x 600 mm and interchangeable, so ROC100 in the office area and ROC200 in the server room can share one floor. Static load is tested to CISCA 2007, EN 12825 and PSA MOB PF2 PS/SPU, with 72 hours of ISO 9227 salt spray and ASTM D5116 for low VOC.
Values as published in the manufacturer's datasheets
Datasheets (PDF from Rhino)

Related projects
- G Tower กรุงเทพฯ: RhinoROC 21,000 ตร.ม.
- UOB กรุงเทพฯ: 2 อาคาร 40,300 ตร.ม.
- สำนักงานใหญ่ Citibank กรุงเทพฯ 27,000 ตร.ม.
- All case studies
Further reading
- How to choose a raised access floor
- Raised floors for server rooms and data centres